Siemens MAG8000 / SP2A
The ADC1 part number has been superseded by the SP2A.
Wiring an SP2A device to a Siemens MAG8000 meter:
Required:
1 x AGRO Brass Cable Gland and reducer (available from Siemens or Taggle)
1 x Sylgard potting kit (available from Siemens or Taggle)
1 x ADC1 with fly-lead (shielded cable)
Remove brass bung on side of meter head, and replace with Brass Cable gland.
Feed SP2A cable through gland into meter. If using shielded cable, make sure the shield is mounted under the cable clamps.
Figure 1 (SIEMENS SITRANS F M – Operating Manual)
Wire in Taggle according to the below diagram
NB3D (connectorised) M12 plug wiring (MAG8000 pulse output)
When a Siemens MAG8000 is connected to an NB3D connectorised device via the 5‑pin M12 sensor plug, wire it as a uni-directional C&I meter (2‑wire pulse output).
M12 Pin | Function | Connect to MAG8000 |
|---|---|---|
1 | Tamper | Link to Pin 3 (Ground) to close tamper loop (required for 2‑wire devices to exit Flight Mode) |
2 | Pulse | Pulse (+) |
3 | Ground | Pulse (-) and link from Pin 1 |
4 | Direction | Not connected |
5 | None | Not connected |
Reference: NB3D Installation Guide – ‘Uni-directional C&I Meter (2 wire)’: NB3D Installation Guide
Figure 2 - Wiring Diagram
Figure 3 (SIEMENS SITRANS F M – Operating Manual)
Sources:
SIEMENS SITRANS F M – Operating Manual
Electromagnetic water meter type MAG 8000 http://support.industry.siemens.com/cs/document/109769781/sitrans-mag-8000?lc=en-ww