Siemens MAG5100

Siemens MAG5100

Siemens MAG5000/MAG6000 to Taggle ADC1-C4-2

 

Safety Note: Only qualified personnel should perform wiring or repairs, and only when the transmitter is not powered. Install transmitter in accordance with all relevant NEC and local codes.

 

Wiring Instructions

 

Terminal 56                         →          ADC1 Pulse Count (Red)

Terminal 57                         →           ADC1 Ground (Blue)

How to set the parameters in your Siemens meter

 

Recommended Settings

Menu item

Recommended Setting

Menu item

Recommended Setting

Volume/pulse

Up to DN100:                    10 L (or 0.01KL)

DN100 to DN450:             100 L (or 0.1KL)

DN500 and over:              1000 L (or 1KL)

Pulse Output

Unidrectional

Pulse Width

66ms

Pulse Polarity

Positive

Pulse Output Time constant

0.1s

 

Note The Siemens MAG51000 only has outputs for forward flow. This may be different from the totalised flow displayed on the meter.

 

Additional Information

PDF

  • 7.1 - Terminal outputs - Passive 56/57

  • 7.2 - Schematic of Terminal Blocks (internal)

  • 8.1 - Keypad and display instructions

  • 8.4.2 - Outputs - Digital Outputs

 