NB3D device H5000 Wiring Guide

NB3D device H5000 Wiring Guide

 

Wiring a Taggle NB3D device to a H5000 meter configured for a pulse output that represents compensated flow.

Step 1:

Check the output pulse on the H5000.

 The H5000 has two pulse output channels – CH1 and CH2. What each pulse represents is marked on the grey shroud.

The meter in the figure below reads:

CH1: 10 L/P F-R

CH2: 100 L/P F-R

 

image-20240610-014039.png

 

The F-R printed implies it is a compensated flow meter. This guide only applies to compensated flow meters.

The inside of the lid should have a sticker on it that gives the colour coding of the different wires.

In the example below:

BLACK = GND Pulse

RED = CH1 Pulse

BROWN = CH2 Pulse

WHITE = Direction/Tamper

In this example, for interfacing with the NB3D Taggle device, either the red or brown wire is used depending on the required litres/pulse.

Step 2: Connect the Taggle M-12 Plug to the H5000.

The cable should be wired to the NB3D using an M-12 plug

 

image-20240610-014130.png

M-12 Plug

H5000 Cabel

Pin 1 - local loop back to Pin 3 (Ground) to ground the tamper loop.

-

Pin 2

Connect to brown (CH1) or red (CH2) wire for required K factor as shown on shroud

Pin 3

Ground (Black)

Pin 4

Leave disconnected.

 

Step 2: Connect the Taggle M-12 Plug to NB3D Device and follow the activation Process